Vue de la page 42
Software/Programming
EXAMPLE 2 (continued)
8.3.4.2 The FAIL-SAFE STATE table controls the RTU outputs when the RTU detects a loss of
RF link. Because Example 2 has two entries in the SEND LIST, both FAIL-SAFE states
A & B are used. If RTU ID 1 detects a loss of RF link from RTU ID 2, outputs are
controlled according to FAIL-SAFE STATE A. If RTU ID 1 detects a loss of RF link from
RTU ID 3, outputs are controlled according to FAIL-SAFE STATE B.
8.3.4.3 I/O CONFIG is Input/ Output control of the RTU displayed in the Programming Software
I/O configuration screen.
8.3.4.3.1 In Example 2, RTU ID 1, Input 1 and Input 2; RTU ID 2, Input 1 and RTU ID3, Input 1
are configured to be inverted digital inputs.
8.3.4.3.2 In Example 2, all four outputs of RTU ID 1 are used, RTU ID 2, Digital Output 1 is used,
and RTU ID 3, Digital Output 1 is used. The initial condition  the state an output is
forced to upon power-on  is set for all relays to be open and all analog outputs to be
forced to 0 scale.
8.3.4.3.3 In Example 2, FROM ID is the ID number of the transmitting RTU; FROM ID numbers
are listed in the following 2 charts:
RTU ID 1 FROM ID (Transmitting RTU ID)
Digital Output 1 2
Analog Output 1 2
Digital Output 2 3
Analog Output 2 3
RTU ID 2 &RTU ID 3 FROM ID (Transmitting RTU ID)
Digital Output 1 1
8.3.4.3.4 FROM LOC is the number of the input controlling the output; FROM LOC numbers are
listed in the following chart:
RTU ID 1 FROM LOC (Controlling Input)
Digital Output 1 1
Digital Output 2 1
Analog Output 1 2
Analog Output 2 2
( B-18 )
Vue de la page 42
1 2 ... 38 39 40 41 42 43 44 45 46 47 48 ... 62 63